1. Introduction

Air movement can play an important role in the thermal comfort of man and beast. A breeze on a humid summer day can make a significant difference to one's thermal comfort. Recent strategies for improving energy-efficiency in buildings attempt to take account of the cooling effects of air movement from natural ventilation. When the building envelope is closed for air conditioning, local air movement is kept below 40 ft/min. This ignores the option of increased air movement to reduce the cooling energy in air conditioned space. This paper explores opportunities for saving energy by utilizing the effects of indoor air movement.

2. Cooling energy savings in air conditioned space from elevated air speed

The current edition of ANSI/ASHRAE Standard 55-2004 Thermal Environmental Conditions for Human Occupancy (ASHRAE, 2004), provides for limited increases of summer thermostat temperature settings by increased local air speed. Figure 1 is derived from Figure 5.2.3 in the Standard 55-2004.

The curves of equal heat loss from the skin for combinations of operative temperature and air movement are referenced to the upper limit of the comfort zone (PMV= +0.5). Limits of 160 fpm and 5.4ºF are set for sedentary activity, 1.0 to 1.3 met. Large individual differences in preferred air speed
requires that occupants have personal control of air speed in increments of 30 ft/min.

The Standard states that it is acceptable to interpolate between these curves. Air speed is more effective at offsetting increases in temperature when mean radiant temperature is greater than the mean dry bulb air temperature.

It should be noted that there are two errors in Figure 5.2.3 of the Standard. The "18°C" should read "18°F" and there is a scaling error between the fpm and m/s scales.

Five separate curves are provided to accommodate temperature differences of -18°F, -9°F, 0.0°F, +9°F, and +18°F between mean radiant temperature, tr , and mean dry bulb air temperature, ta. The writer fitted equations to the portion of the curves limited to sedentary activity of 160 fpm and 5.4°F for 1.0 met to 1.3 met and 0.5 to 0.7 clo.

The writer also fitted equations to the portion of the curves for activity beyond the sedentary limits. Cooling effect limits for these equations fitted to curves in Figure 5.2.3 in the Standard 55-2004 were 300 fpm and 8°F.

2.1 Curve for tr - ta = 0.0 K

For tr - ta = 0.0°F, an air speed of 160 fpm permits a thermostat set point increase of 4.4°F limit for light sedentary activity (1 to 1.3 met) and 0.5 to 0.7 clo.

V = 40 + 6.8”t 1.85 (1)
Where V is the mean relative air speed in fpm and ”t is the cooling effect in °F.

In most thermostatically controlled air conditioned spaces, wall, ceiling and floor surfaces temperatures are close to air temperature. That is tr - ta = 0°F. Conditions when tr -- ta is not zero include spaces with poorly insulated windows, walls or ceilings where the outer surface is exposed to direct solar radiation or cold winter conditions.

2.2 Curve for tr - ta = +9°F

For tr - ta = +9°F an air speed of 160 fpm permits a thermostat set point increase of 5.4°F limit for light sedentary activity (1 to 1.3 met) and 0.5 to 0.7 clo.

V = 40 + 1.26”t 2.85 (2)
Where V is the mean relative air speed in fpm and ”t is the cooling effect in °F.

2.3 Curve for tr - ta = +18°F

For tr - ta = +18°F an air speed of 126 fpm permits a thermostat set point increase of 5.4°F limit for light sedentary activity (1 to 1.3 met) and 0.5 to 0.7 clo.

V = 40 + 1.28”t 2.7 (3)

3. Beyond Sedentary Activity limits

The Standard is not clear on constraints for the portions of the curves up to 89°Fand 300 fpm, beyond the limits set for sedentary activity. Studies have measured the cooling effect of air movement up to 600 fpm in warm climate conditions (Khedari et al, 2000, Tanabe and Kimura, 1994, and Scheatzie et al, 1989). Air movement higher than 160 fpm is used in air conditioned gymnasia and shopping malls to augment cooling of occupants. The writer has fitted equations to the portion of the curves for activity beyond the sedentary limits

For tr - ta = 0.0°F an air speed of 300 fpm indicates the thermostat set point increase could be 6.6°F at activity levels higher than 1.3 met.

V = 40 + 2.52”t 2.5 (4)

Limits for Equation 4 are 160 fpm to 300 fpm and 4.4 F to 6.6 F

For tr - ta = +9ºF an air speed of 276 fpm permits a thermostat set point increase of 8ºF at activity levels higher than 1.3 met.

V = 40 + 5.7”t 1.8 (5)

Limits to Equation 5 are 160 fpm to 280 fpm and 5.4ºF to 8ºF .
For tr - ta = +18ºF an air speed of 211 fpm indicates the thermostat set point increase could be 8ºF at activity levels higher than 1.3 met.

V = 40 + 6.3”t 1.59 (6)

Limits for Equation 6 are 132 fpm to 209 fpm and 5.48ºF to 8ºF.

4. Estimating Cooling Energy Savings

The electrical US utility corporation Exeloncorp (2005), suggests that domestic air conditioning cooling costs can be reduced by 3% to 4% for each ºF that the thermostat setting is raised in summer.

Occupants can offset an increased thermostat setting of 4.7ºF by providing 160 fpm of low-cost air flow from circulator fans and enjoy normal comfort while saving air conditioning operating cost. On the basis of the Exeloncorp (2005) recommendation, an increase in the thermostat setting of 4.7ºF would provide cooling energy savings from 14% to 19%. In gymnasia where higher air movement is acceptable the savings from a thermostat increase of 8ºF could be from 24% to 32%. A detailed analysis of reduction in residential cooling loads due to air flow was performed for six US cities in a variety of climate zones (Byrne and Huang, 1986)

5. Comparison of fans and room air conditioners

A detailed comparison of the energy required to maintain the same thermal comfort in a 141.5 ft2 bedroom in Townsville, Hope (2003), was conducted using a 55 inch diameter residential ceiling fan and a VF100C Carrier window/wall room air conditioner, sized for the room by engineers at the local distributor. The measured rate of power consumption of a 55 inch diameter ceiling fan operating at its top speed was 0.068kW or 0.48 W/ft2 of floor area. This is 8.7% of the power used by the room air conditioner to achieve the same thermal comfort. The rate of power consumption of the window/wall room air conditioner was 0.78 kW, or 5.51 W/ft2 of floor area. This is 11.5 times the power used by the ceiling fan.

6. Destratification

In heated spaces in winter, indoor air tends to stratify with the hottest, less dense, air accumulating under the roof due to the gravity force. This condition creates two problems. Firstly the hottest air is not contributing to the thermal comfort of occupants near floor level, and secondly, it creates a high temperature difference between the underside of the roof and the exterior of the roof that increases heat losses through the roof.

Destratification is the process of thoroughly mixing indoor so that air temperature near the floor is the same as the air temperature under the roof, or no more than 2ºF difference. This is done using circulator fans. In a typical US distribution warehouse with a 30 ft high ceiling, the seasonal heating energy savings from effective destratification is around 20% to 30%. To be effective about one half of the total volume of air in the space needs to be moved from ceiling level to floor level per hour.

To be effective in destratification the fan should be no more than 1 diameter below the ceiling and the jet from the fan must impact on the floor in order to achieve effective circulation. Jets from ceiling fans have an effective throw of 5 to 6 diameters.

In large buildings with high ceilings such as churches, industrial buildings or distribution warehouses, a large volume of air needs to be circulated. In order to avoid complaints of drafts from occupants, the local air velocity at head height needs to be kept less than 40 ft/min.

Circulator fans are much more energy-efficient at low speeds, so large diameter, slow moving, fans are well suited for destratification. One 24 ft diameter industrial ceiling fan operating at top speed of 42 rpm uses 1.67 kW of electrical power but only 0.06 kW operating at 14 rpm its peak efficiency. At 42 rpm this fan delivers around 337,700 cfm of air and 76,670 cfm at 14 rpm. An added benefit of operating large fans at low speed compared to smaller fans at higher speeds is the reduction in fan noise. Large slow moving fans are virtually silent.

7. Estimating Destratification Energy Savings

A recommended method for estimating heating energy savings from destratification is to determine the lumped seasonal heat transfer rate for the building envelope and determine the difference in heat loss before and after destratification (Pignet and Saxena, 2002).

The lumped seasonal heat transfer rate for the building envelope in Watts can be calculated using:

A x U = qbd / (ti -to) (7)

Where: A is the surface area of the building envelope in ft2; U is the lumped heat transfer coefficient for the building envelope in Btu/ft2.h.ºF; qbd is the rate of heat loss through the building envelope in Btu/h before destratification; and ti -to is the average heating season indoor to outdoor air temperature difference in ºF.

The total heat lost from the building is the sum of heat released from furnaces plus heat released in the space from other sources such as lighting, people, machinery or manufacturing processes. The heat released from the furnaces can be determined from the fuel bills for the season, the caloric value of the heating fuel and the system efficiency. The caloric value of natural gas is around 1000 Btu/ft3. The time used in these calculations is the heating season associated with the measured fuel consumption.

Forced air furnaces with flues have efficiencies around 0.7. Radiant heaters without flues have an efficiency of 0.8. Electrical heaters have an efficiency of 1.0. Heat from other sources is estimated in the normal way as set out in HVAC handbooks (ASHRAE, 2005).

With the overall heat loss U x A for the heating season before destratification determined, the reduction in heating after destratification, qad can be determined from:

qad = U x A x (tibd - tiad) (8)

Where: qad = Reduced heat load after destratification in Btu/hr; U = Lumped time-averaged heat loss rate for the building envelope in Btu/hr.ft2.ºF ; A = Surface area of the building envelope, ft2; tibd = Heating season average indoor air temperature before destratification,,°F;; This depends on vertical temperature profile. This should be measured on site because the shape of the temperature profile can vary substantially depending on type of heaters, their height above floor level, and how ventilation is provided; tiad = Heating season average indoor air temperature after destratification, °F. This is taken as the thermostat set point as the indoor air temperature throughout the space is close to uniform after destratification.

The reduced heating load due to destratification can be converted into a quantity of fuel taking into account the efficiency of the heating system and the caloric value of the fuel. The heating fuel cost saving typically between 20% and 30% is calculated using the unit cost of fuel.

8. Thermal comfort in Non-air Conditioned Space

The ANSI/ASHRAE 55-2004 Standard offers a method for determining an acceptable range of indoor operative temperature in occupant-controlled, naturally conditioned spaces. Occupant-controlled, naturally conditioned spaces are defined as spaces where thermal conditions of the space are regulated primarily by the occupants through opening and closing windows. These are spaces with no refrigerated air conditioning, radiant cooling, or desiccant cooling. Fans can be used when natural ventilation does not provide sufficient air movement.
In such spaces, occupants have different expectations of thermal comfort and accept wider ranges of thermal conditions in both winter and summer than occupants of air conditioned spaces. This method is intended for climates where mean monthly air temperatures fall in the range of 50°F to 92°F. This method is generally described as the Adaptive Model (de Dear and Schiller (2001).

Using the adaptive approach, the first step is to determine the average monthly temperature for each month of the cooling season for the location. In ventilated buildings without air conditioning, temperature for operative comfort toc, is based on mean monthly outdoor air temperature tout, and can be calculated using the following equation (ASHRAE, 2005).

toc = 66 + 0.255(tout - 32) (9)

The comfort zone range of operative temperature to satisfy 80% of acclimatized people can be read of a graph in the Standard or by adding and subtracting 6.3 ºF to the operative comfort temperature.

With a mean daily air temperature of 83.6ºF in the city of Houston during July, toc = 66 + 0.255(83.6 -32)= 79.2 ºF. The thermal comfort zone to satisfy 80% of people in July is then 72.9ºF to 85.5ºF.

Given the long term average monthly outdoor air temperature for Houston TX in July is 83.6ºF, this presents the average need for a cooling effect from air movement in January of 83.6ºF - 79.2ºF or 4.4ºF to restore the operative temperature to the norm. The question now is how much air movement is needed to achieve a cooling effect of 4.4ºF? Using the data from Khedari et al (2000), for a warm humid climate with a relative humidity of 75% indicates 87 fpm is needed for a 4.4ºF cooling effect.

9. Cooling effects of air movement in naturally conditioned spaces

The US Naval Medical Command (1988) in a chapter on relieving heat stress published data on the relative cooling effect of air movement Figure 7. These data do not provide a quantitative cooling effect but are useful in that they indicate the maximum cooling effect occurs with air movement around 1,500 fpm.

In naturally conditioned space, there is no control of humidity. As the cooling effect of air movement in warm environments relates to evaporative cooling from sweating, it has been shown that as humidity increases, the cooling effect of air movement decreases. The reduced cooling effect is much greater in warm humid environments when air movement needed for thermal comfort exceeds 295 fpm, Figure 6 (Khedari et al, 2000). It is important to use cooling effect data derived from local climate and cultural conditions. These data will better reflect the thermal comfort expectations of local people taking into account local dress and typical levels of metabolic activity.

A variety of approaches have been taken by researchers to quantify the cooling effects of air movement. Cooling effects of air movement can effective in hot arid environments were evaporative cooling of the skin is not encumbered by high humidity (Scheatzle et al, 1989).
Another equation derived from several studies (Szokolay, 1998) that is widely used for estimating the cooling effects of air movement from 40 ft/min to 400 ft/min is:

”t = 10.8((V/197.85)-0.2)-1.8((V/197.85)-0.2)2 (11)

Where V is in ft/mim and ”t is in ºF.

Using this equation, air movement of 400 ft/min provides a cooling effect 13.7 ºF. This is equivalent to Khedari et al cooling effect for 400 ft/min at 57% relative humidity in Thailand.

10. Indoor air movement for livestock

Dairy farmers have learned from university studies that thermally comfortable cows' milk production, reproductive health and growth are much better than those of cows subjected to summer heat stress (Sanford, 2004). During hot summer periods dairy farmers have installed small high speed circulator fans to achieve the recommended air movement of 177 ft/min to 433 ft/min. Ten 36 inch diameter fans operating at 825 rpm use 3.73 kW of electrical energy. Farmers have found they can replace 10 of these 36 inch diameter fans with a single 24 ft diameter fan operating at 42 rpm that uses only 1.6 kW of electrical energy while providing the same air movement. Additional cooling can be achieved in drier climate regions using misting water sprays for evaporative cooling.

11. Discussion

All the descriptions of air movement described so far in this document have referred to the average velocity of air movement. Olesen (1985) refers to a study by Fanger and Pedersen of the chilling effect of winter draughts. It was observed in the study that the chilling effect of gusting air flow reached a peak around a gust frequency of 0.5Hz.

More recently researchers in China (Xia et al,2000) repeated these studies inwarm, humid conditions with temperatures ranging from 79ºF to 87ºF and relative humidity between 35% and 65%. These experiments showed that the preferred gust frequency for cooling air movement was between 0.3Hz and 0.5Hz. Approximately 95% of subjects preferred gust frequencies below 0.7Hz. Natural breezes and air flow from large low-speed circulator fans have a significant portion of their energy spectral density around this frequency of 0.5Hz. Olesen (1985) suggested the use of an equivalent uniform air velocity, Table 1, to account for this effect but this enhanced cooling effect has not been specifically accounted for in cooling effects of air movement to date.

12. Conclusions

Current air conditioning design provides for uniform air temperature and humidity throughout a space, with imperceptible local air movement in the occupied zone of less than 40 ft/min. This conventional design is based on air conditioning heating and cooling loads that ignore the substantial savings to be gained from increased indoor air movement from circulator fans.

Recent ASHRAE acceptance of an adaptive thermal comfort model clearly shows that people who live in air conditioned houses, drive air conditioned cars, work in air conditioned offices impair their natural thermal comfort adaptation. This impairment results in unnecessarily high summer cooling loads.

Where naturally conditioned buildings are acceptable, indoor thermal comfort can be achieved with substantial energy savings by better utilization of indoor air movement.

The cooling effect of air movement has been well established by a number of researchers. There remains a need for further research on the cooling effects of air movement on building occupants to accommodate activity levels beyond 1.3 met, higher air velocities for non-sedentary activity, and lighter clothing levels than 0.5 clo. This research is needed in both air conditioned and naturally conditioned spaces.

Research on the cooling effects of air movement has been presented in many forms. The chart produced by Khedari et al (2000) is one the better formats. Further research is needed to develop a form which presents data in a way that makes it more easily used by engineers to improve energy efficiency with increased indoor air movement.

The same circulator fans used to enhance summer thermal comfort can be used to destratify indoor air to save heating energy in winter. This particularly applies to commercial or industrial spaces with high ceilings.

References

ASHRAE (2005) ASHRAE 2005 Handbook of Fundamentals, ASHRAE, Atlanta, GA. Page 26.11.

ASHRAE (2004) ANSI/ASHRAE Standard 55-2004 Thermal Environmental Conditions for Human Occupancy. ASHRAE, Atlanta, GA.

Byrne, S. and Huang, V.(1986) The impact of wind-induced ventilation on residential cooling load and human comfort. ASHRAE Trans. Vol.92, Pt. 2, 793-802.

de Dear, R. and Schiller Brager, G. (2001) The adaptive model for thermal comfort and energy conservation in the built environment. Int. J. Biometeorology, 45: 100-108.

Exeloncorp (2005) Controlling Temperatures is accessible on the internet at:
http://www.exeloncorp.com

Fountain, M. (1995) An empirical model for predicting air movement preferred in warm office environments. Standards for thermal comfort: Indoor air temperatures for the 21st century. Edited by F. Nicol, M. Humphreys, O. Sykes and S. London, Roaf, E & F Spon. pp. 78-85.

Hope, P (2003) Energy efficiency ratings: Implications for the building industry in the humid tropics. Master in Tropical Architecture dissertation, Australian Institute of Tropical Architecture, James Cook University, Townsville, Australia, pp. 377.

Khedari, J., Yamtraipat, N., Pratintong, N. and Hinrunlabbh, J. (2000) Thailand ventilation comfort chart. Energy and Buildings, Vol. 32, pp. 245-249.

Naval Medical Command (1988) Manual Of Naval Preventive Medicine, Chapter 3, page 3-7. Accessible on the internet at:
[http://www.vnh.org/PreventiveMedicine/PDF/P-5010-3.pdf]

Olesen, B. (1985) Local thermal discomfort. Bruel & Kjaer Technical Review, No.1, Denmark, pp.3-42.

Pignet, Tom and Saxena, Umesh (2002) Estimation of energy savings due to destratification of air in plants, Energy Engineering, Vol 99, No. 1, 69-72.

Sanford, S. (2004) Energy conservation in agriculture: Ventilation and cooling systems for animal housing. University of Wisconnsin Cooperative Extension publication A3784-6, pp.3.

Scheatzle, D., Wu, H. and Yellott, J.(1989) Extending the summer comfort envelope with ceiling fans in hot, arid climates. ASHRAE Trans. Vol.100, Pt. 1, 269-280.

Szokolay, S. (1998) Thermal comfort in the warm-humid tropics, Proceedings of the 31st Annual Conference of the Australian and New Zealand Arch. Science Association, Uni. of Queensland., Brisbane, Sept.29-Oct.3, pp. 7-12.

Tanabe, S and Kimura, K. (1994) Importance of air movement for thermal comfort under hot and humid conditions. ASHRAE Trans. Vol. 100, Pt. 2, 953-969.

Xia, Y., Zhao, R. and Xu, W. (2000) Human thermal sensation to air movement frequency. Reading, UK. Proceedings of the 7th International Conference on Air Distribution in Rooms. Vol.1, pp. 41-46.


Improve Energy Efficiency - Saving Energy With Indoor Air Movement

Comparison Folding Cloth Diapers !8!# Great Deals Billy Goat Leaf Blower

Tuesday, October 25, 2011

Home Energy Savings: New House Design and Energy Conservation

!±8± Home Energy Savings: New House Design and Energy Conservation

Consumers in North America are getting ready for the 2005 / 2006 winter season as we write this report and most are bracing themselves for larger energy bills during the coming winter heating season than past years. Recent spikes in energy costs for all types of energy including gasoline, heating oil, electricity and natural gas are causing many consumers to begin thinking about how they heat their homes and whether they can save money. In our discussion we will use the term "energy" to refer to all of the previous forms of fuel that is used in our homes.

Energy conservation begins with the design and construction of a new home and carries through to your daily living habits. Consumers who have the most success in terms of reducing their energy bills have made energy conservation a way of life, while enjoying their new homes in comfort.

Many homeowners have the potential to reduce their heating bills by as much as 50% or more. They can achieve these savings with a logical, well planned approach beginning with the design of the home, proper construction techniques, well insulated windows, doors, and walls and then follow through with daily, monthly and annual operational techniques.

Consumers who have designed and insulated their home with energy conservation in mind will be able to maximize their savings if they make energy conservation part of their every day life. The common objectives of living in a comfortable home and managing your energy consumption can easily be met by following a few simple rules.

Systems Approach to Energy Savings

Our homes are really a complex environment that must be managed to ensure that we live comfortably, have sufficient fresh air, while controlling our energy consumption at the same time. Essentially, a well planned home will take into account the amount of energy intake from energy sources such as our heating system as well as solar heating vs. energy loss from the effects of cold weather, heat loss through windows, doors, walls and floors as well as heat reduction when we use air conditioning systems in hot climates.

In the winter we are concerned about the cost of heating our homes and the loss of heat to the outside through leakage of cold air into our homes. The summer brings the reverse when we must cool our homes and manage the cooling during hot summer days. In both cases solar heat plays a part in the equation as well as how well sealed our homes are. Consumers living in colder climates will be more concerned about winter heating costs while consumers living in southern areas of the continent will worry about the cost of air conditioning.

Taking a systems approach to managing your energy costs is one way to ensure that you maximize your savings and make a positive contribution to the environment through reduced energy usage. Energy conservation and home design begins with the orientation of your home to maximize the heating of your home by natural solar heating in colder climates and avoiding solar heating in hot climates. Next, consumers can take advantage of natural shade or by adding trees to provide shade during hot summer days and also act as wind breaks to reduce the impact of the cooling effects that the wind can have on the amount of energy they use.

Once you have considered these elements, consumers should use the latest techniques in designing their homes with high insulation values in the walls, energy efficient heating and cooling systems as well as energy efficient appliances. For example your air conditioning unit should be energy efficient and placed were it will be in the shade as much as possible to maximize its efficiency. Selection of fluorescent lighting, taking advantage of natural lighting are additional elements to be considered in the design of your new home. Visit our home energy checklist for more details on steps you can take to reduce your energy costs at the design stage of your home.

Consumers may also want to invest in an energy audit of their homes design before agreeing to the final design. A relatively low cost audit can sometimes save thousands of dollars in energy costs over the life of their home.

Our Home Energy Checklist

We have assembled a home energy checklist with both the new home buyer / builder in mind as well as items to check after you have moved in. Our objective is to assist you in saving energy, which means money in your pocket during the design as well as after you have moved into your new home. Saving energy can be divided into four areas: Home Design; Appliance & Lighting Selection, Energy Conservation - A Way of Life. This total systems and life style approach is really geared to maximizing your energy savings.

You might have the most efficient energy saving home built, however if you move in and leave all of the lights on all the time, leave the windows open when you are heating the house or cooling, your energy saving initiatives will not be as affective as you might have thought.

With this in mind our energy savings checklist applies to the design phase as well as after you have moved into your new home. Even consumers who have been in their homes for a few years will find this checklist useful for managing their energy consumption.

Designing New Homes and Energy Conservation

Most home designers and architects are up to date on energy conservation techniques, however they are also geared to meeting their customers needs and priorities for their home designs. Many consumers will consider home energy management almost as an after thought when it is too late to incorporate energy savings concepts into their new home design. As you and your home designer or architect discuss your plans and your objectives for your new home, always emphasize that energy management and home comfort are a very important element of the final design that your are looking for.

Designing a new home actually begins with site selection and orientation of your home on the property. Depending on the climate consumers will want to orient their homes on the property to manage the amount of solar heating that the house will be exposed to. A common theme throughout this report is to orient your home so that the sun can heat the home naturally in the winter, while minimizing the effects of solar heating during hot summer days. Adding trees or shrubs to provide shade and taking advantage of natural land formations to provide shelter from prevailing winds is the first step in managing your energy costs.

Construction of the foundation for homes varies a great deal across the continent. In some locales a below grade basement is mandatory, while in other locations a concrete slab is standard. In both situations, insulation is a key component to maintain comfortable living conditions while reducing your energy costs. Insulation can be added below the slab of concrete and all basement walls should be properly sealed and insulated to at least R20 levels. All exposed hot water pipes can be insulated as well in addition.

Walls should be insulated to at least R20, while attics should have insulation to a level of R40. Floors over crawl spaces will be warmer and you will lose less energy if the floors are also insulated. Many customers will select wall to wall carpeting for additional insulation and warmth, however if you prefer ceramic, marble or hardwood floors, area rugs can be used as decoration as well as providing a warm surface to walk on. Ceiling fans are another inexpensive way to distribute naturally heated air.

Consumers can select windows and doors that are energy rated with triple pane windows and insulated steel doors. Adding a storm door to the outside increases the level of insulating and energy savings that you can achieve. During the winter consumers will enjoy the warmth of the suns ray's through the windows, while summer months the windows can be covered to reduce the heating affects of the sun. Selection of window coverings, while meeting aesthetic requirements can also support energy saving concepts as well.

The selection of lighting fixtures with fluorescent lighting and also taking into account natural lighting can reduce your lighting costs significantly. Incorporate timers, motion detectors, photo cells at appropriate locations in your home to assist in managing your lighting needs as well as energy usage.

Bathroom design as well as all areas were water is used should incorporate flow restrictors to minimize the use of cold and hot water.

Everyone loves to have a fireplace in their home. A fireplace can generate a huge loss of energy if not managed properly and designed with energy conservation in mind. Natural wood burning fireplaces have the lowest efficiency, while sealed gas fireplaces can be very efficient, while still providing the ambiance that many consumers are looking for.

The selection and use of your appliances can have a significant impact on your energy costs. Old appliances may be energy guzzlers, while new appliances should be chosen based on their energy ratings. Selecting a high efficiency furnace, air conditioner and water heater is a first step. Consider purchasing new appliances instead of moving your appliances from your last home. Electronic ignition of gas appliances, taking advantage of shade for your air conditioner and using a digital thermostat that allows timed control of your homes interior temperature are all elements of the energy design of your home.

One final comment about new home design is in order. Consumers may also want to arrange for an energy audit of their home before they agree to the final design. Suggestions by an expert quite often will pay for the cost of the audit in terms of energy savings.

Energy Conservation - A Way of Life

Consumers who go to the time and expense of designing and building an energy efficient home may be disappointed with the savings that they obtain if they do not practice energy conservation in their daily lives. For example, you may have paid for a well insulated home, sealed all the cracks, used caulking were you were supposed to and installed the best windows and doors. If you then leave windows open, forget to turn down the thermostat on cold winter days when you are not at home or turn up the thermostat on hot days, you may not achieve the savings that you were expecting. Leaving lights on, running appliances with partial loads e.g. the dishwasher etc can also increase your energy consumption beyond what you may have been expecting.

Our home energy checklist covers many items that home owners can consider as a means of taking advantage of all of the energy efficient attributes of their home to reduce their energy consumption even further. Making this approach part of your lifestyle will ensure that your energy savings continue after you have moved in to your new home and lived there for sometime.

Many people are also concerned about the impact of conserving energy on their comfort and may be afraid to implement some energy saving concepts. We would like to politely point out that replacing an incandescent light with a fluorescent light will not only save you energy, but provide you with a more comfortable light in your home as well. Filling up the dishwasher or the clothes washer before running them takes no additional effort on your part and saves you energy usage at the same time. There are many examples such as these that will reduce your energy consumption and not impact your comfort. In fact plugging leaks and designing ceiling fans into the home can positively improve the aesthetics as well as reduce drafts.

Review our home energy checklist and apply those items that impact your situation. You will be amazed at how much you can save by following a few simple steps!